Portable Power Station Runtime & Capacity Calculator

Plan appliance hours, efficiency and reserve charge to estimate required Wh.
Compare simultaneous loads, startup power and two product quotes in KRW.

Starting values are fictional. Enter your appliances and specifications and quotes for two products.

Compare AC outlet use with the inverter on throughout and no recharging. Times are hours elapsed from the start. All money is KRW; convert foreign quotes consistently first.

1. Plan between charges

Reserve must be below starting charge. Retention of 80% means you assume 80% of nameplate capacity remains; it is not an automatic temperature or lifetime estimate.

2. Appliance schedule and power

Enter 0 for unknown startup power. Start plus duration must fit within the plan. Duty cycle reduces estimated energy only; running and startup watts still determine output requirements.

Device 1

Planned appliance energy: 360 Wh

Device 2

Planned appliance energy: 160 Wh

Device 3

Planned appliance energy: 120 Wh

3. Compare two power stations

Adjust efficiency for the product and load. Idle draw is battery-side W. Set idle to 0 if your measured efficiency already includes standby losses. Surge is a separate rating; enter 0 if unknown.

Product A
Product B

Energy and output needed for your plan

Total appliance energy
640 Wh
Peak running output
120 W
Simultaneous startup envelope
360 W

Startup envelope assumes every appliance in the same window restarts together. Product capacity estimates below include efficiency and idle draw.

Product A · Example / unconfirmed

Energy-only runtime to reserve

10.49 h

Reserve reached during the plan

Within entered W limits. Confirm surge duration, voltage, frequency, waveform and VA/power factor with the manufacturer.

Required nameplate capacity (rounded up)
956 Wh
Nameplate capacity shortfall
155.56 Wh
Usable battery before reserve
720 Wh
Planned battery-side demand
860 Wh
Battery energy margin (negative = shortfall)
-140 Wh
Continuous output check
Meets entered value (180 W)
Surge output check
Meets entered value (240 W)
Quote including extras
KRW 650,000
Budget margin (negative = over budget)
KRW 150,000

Product B · Example / unconfirmed

Energy-only runtime to reserve

≥ 12 h

Enough energy for the entered plan

Within entered W limits. Confirm surge duration, voltage, frequency, waveform and VA/power factor with the manufacturer.

Required nameplate capacity (rounded up)
857 Wh
Nameplate capacity shortfall
0 Wh
Usable battery before reserve
1,350 Wh
Planned battery-side demand
771.11 Wh
Battery energy margin (negative = shortfall)
578.89 Wh
Continuous output check
Meets entered value (880 W)
Surge output check
Meets entered value (1,640 W)
Quote including extras
KRW 1,000,000
Budget margin (negative = over budget)
KRW -200,000

B − A quote difference: KRW 350,000. Positive means B costs more. Compare capacity, output and verification status together.

Energy by usage interval

Load and product battery demand in each interval
Elapsed time (h)Average load (W)Load energy (Wh)A (Wh)B (Wh)
0230608576.67
2490180235210
4830120170153.33
81270280370331.11

A/B columns show demand for the complete plan, including intervals after reserve is reached. Duty cycle averages energy; it does not predict actual restart times.

Sources checked: 2026-09-15. Excludes direct DC/USB, recharging, medical life support, fixed electrical installations and UPS suitability. Check the exact model manual and measured appliance consumption.

Start with a plan between charges

A fridge overnight, evening lights and a laptop create a different load at different times.
This portable power station runtime and capacity calculator adds those usage windows, then compares two products using their storage, output, efficiency and quotes.
It separates an energy shortfall from an output limitation and an over-budget purchase so you can see what needs to change.

The calculation covers appliances connected to a portable power station through its AC outlets.
It does not estimate phone power-bank charge counts or vehicle starter-battery life.
Starting values are fictional examples, not current product prices or guaranteed performance.
Both language versions use the same calculation; quotes are in KRW, so convert foreign prices consistently before entering them.

Read Wh, running W and startup W separately

Storage and energy: Wh

Watt-hours describe energy over time.
In a fictional loss-free example, 100W for 2 hours requires 200Wh.
The nameplate capacity is only the starting point: charge level, reserve, retained capacity and conversion losses determine how much can serve this plan.

Running and startup power: W

Watts describe the power needed at an instant.
A large battery can still have an inverter that cannot supply the required continuous output.
Appliances with motors may also require a separate startup allowance, and the permitted surge duration matters alongside its watt rating.

Find storage Wh, continuous AC output and surge AC output in the exact model manual.
Do not put an advertised maximum output number into the capacity field.
A voltage-reducing boost feature is not automatically the same specification as surge output; confirm the applicable rating before entering it.

Enter appliance windows and simultaneous use

  1. The total plan is the elapsed time until the next charge.
    For a 12-hour plan, time starts at 0 and ends at 12; these fields are not clock times.
    One plan can cover up to 168 hours, and schedules do not automatically repeat the next day.
  2. Each row contains a device name, quantity and running and startup watts per device.
    Split different appliances, or separate operating windows, into separate rows.
    Enter 0 for an unknown startup value; the corresponding output check will remain unknown.
  3. Start plus duration must fit inside the total plan.
    Lights starting 8 hours after departure and running for 4 hours use start 8 and duration 4.
    A disabled row, zero duration or zero duty cycle contributes no energy or output requirement.
  4. Duty cycle is the proportion of a window during which the appliance consumes its running power.
    For a fictional 60W fridge operating for half of a 12-hour window, enter 50%.
    Do not enter an already averaged low power and then reduce it again with duty cycle; that understates energy.

Quantity multiplies energy, running watts and startup watts.
All devices within one row share the same window, so use separate rows when two appliances alternate.
Names appear in the saved report; use recognizable model or adapter names to make later checks easier.
If you only know measured average power, use 100% duty for energy and separately verify the actual maximum running watts before relying on the output comparison.

Efficiency, idle draw and reserve are distinct

Conversion efficiency and idle draw

Efficiency is the share of battery energy delivered to the load.
The starting 80% and 90% are editable examples, not universal certified values.
Battery-side idle watts apply throughout the plan, including windows with no appliance load, because the model assumes the inverter stays on.
If measured efficiency already includes all standby losses, enter 0 idle watts to avoid counting the same loss twice.

Starting charge and reserve

Starting at 100% and reserving 10% leaves a 90% charge window.
Starting at 70% with the same reserve leaves 60%.
Runtime to reserve is not runtime to a fully discharged battery; the reserved energy is never added back to the plan.
Reserve must be below starting charge.

Capacity retained after cold or aging

Retention is your assumption about the share of nameplate capacity available in the current condition.
At 100%, no additional reduction is applied; 80% assumes only 80% remains.
The calculator does not infer retention from temperature or age, or determine warranty capacity.
Use measured data and guidance for the exact product.

Required capacity and runtime formulas

  • Appliance energy = running W × quantity × window h × duty cycle
  • Battery-side demand = total load Wh ÷ efficiency + idle W × total h
  • Usable battery Wh = nameplate Wh × retention × (starting charge − reserve)
  • Required nameplate Wh = battery-side demand ÷ [retention × (starting charge − reserve)]

Percentages are fractions in these formulas: 80% becomes 0.8.
Required nameplate capacity is rounded upward for display, while sufficiency checks use unrounded values.
Different product efficiencies and idle draw produce different required capacities for the same appliance plan.
Idle watts are already measured on the battery side and are not divided by efficiency again.

The model divides the schedule at every appliance start and end, then accumulates battery demand interval by interval.
Within the interval that would use the reserve, it divides the remaining available energy by that interval’s average battery draw.
If the whole plan fits, the display says at least the entered duration, such as 12 hours, without extrapolating an unentered future schedule.
Meeting demand exactly at the end counts as completing the plan.

Worked example: a 12-hour camping plan

Assume one fictional 60W fridge at 50% duty for 12 hours, two 20W lights for 4 hours starting at hour 8, and one 60W laptop adapter for 2 hours starting at hour 2.
Their energy totals are 360Wh, 160Wh and 120Wh: 640Wh altogether.
With 300W startup for the fridge and startup equal to running power for the other devices, peak running output is 120W and the simultaneous startup envelope is 360W.

A: 800Wh at 80% efficiency

Adding 5W idle draw for 12 hours gives 860Wh of battery demand.
At 100% starting charge, 10% reserve and 100% retention, usable battery energy is 720Wh, a 140Wh shortfall.
Required nameplate capacity is approximately 955.56Wh, displayed as 956Wh.
Reserve is reached at approximately 10.49 hours; nameplate capacity shortfall is approximately 155.56Wh.

B: 1,500Wh at 90% efficiency

With the same 5W idle draw, battery demand is approximately 771.11Wh.
Usable energy is 1,350Wh, enough for the 12-hour plan with approximately 578.89Wh of energy margin.
Required nameplate capacity is approximately 856.79Wh, displayed as 857Wh.
Remaining energy does not guarantee operation through a later schedule that has not been entered.

A’s runtime differs from a simple whole-plan average calculation.
Only the fridge runs during hours 0–2 and 4–8; the laptop adds load during hours 2–4, and lights add load during hours 8–12.
Moving a heavy load earlier can change the time reserve is reached even when the plan’s total Wh stays unchanged.

Interpret energy and output checks in order

  1. Compare battery demand with usable energy first.
    A negative energy margin means the entered plan cannot finish while preserving reserve.
    Nameplate capacity shortfall and battery-side energy shortfall can differ because they use different retention and charge-window bases.
  2. Check peak running watts against continuous AC output.
    A 50% duty appliance still needs its normal running power when it turns on; duty never halves the watt requirement in this check.
    Devices whose windows merely touch are not counted as overlapping.
  3. Compare the simultaneous startup envelope with surge output.
    The envelope conservatively assumes every device in an overlapping window restarts together; it is not a prediction of the usual peak.
    Unknown appliance startup watts or an unknown product surge rating prevent a complete output check, even when the energy estimate looks sufficient.

Passing the entered W limits does not establish compatibility for voltage, frequency, waveform, VA and power factor, port limits or surge duration.
The user-check box records that you reviewed the inputs; it is not a certification.
An averaged duty cycle cannot reproduce the exact timing of compressor starts or protection-circuit behavior.

Compare quotes against the same budget

Include the same costs on both sides

Product A’s fictional KRW 600,000 quote plus KRW 50,000 extras totals KRW 650,000.
Product B’s KRW 950,000 quote plus KRW 50,000 extras totals KRW 1,000,000, so B − A is KRW 350,000.
Against a KRW 800,000 budget, A has KRW 150,000 remaining and B has a −200,000 KRW budget margin.
These are worked-example prices, not a market survey.

Include delivery, required cables, cases and accessories that are missing from the base quote, without double counting included items.
A positive quote difference means B costs more; it does not determine which product has better quality or is suitable.
A can be cheaper yet fail the energy requirement, as in the example.

Unknown fees are not automatically free.
Select a product’s confirmation box only after checking the actual quote scope and specifications.
Use the same currency-conversion basis for both foreign quotes and keep the model name and quote date alongside the downloaded report.
The calculator does not retrieve prices, exchange rates or product inventory.

Practical scenarios and avoiding excess capacity

Fridge and evening lights

Cooling conditions and how often a fridge is opened can change its average consumption.
Adjust the duty assumption using relevant measurements and compare the resulting reserve time.
Reducing lighting hours saves energy but does not remove the fridge’s own startup requirement.

Sequential use and short high-power loads

Move laptop charging or another appliance’s window to reduce overlap.
A high-power device used briefly may consume relatively little Wh while still exceeding the continuous-output limit.
Start with essential devices, then disable optional rows to see how the capacity requirement changes.

If recharging is planned, enter only the no-recharge interval between charges.
Solar panel nameplate watts are not automatically converted into battery energy here.
Turning the inverter off midway also changes the idle assumption, so review such usage separately; within one plan this model keeps idle consumption active throughout.

Frequently asked questions

How long does 1,000Wh last?

You also need the appliance schedule, power, efficiency, starting charge and reserve.
The order of usage can change reserve time even with the same battery capacity.

Does 50% fridge duty halve startup power?

No.
Duty affects average energy only.
Running and startup output checks use per-device watts and quantity without that reduction.

Can I put mAh into the Wh field?

No, the units differ.
Prefer the manufacturer’s stated Wh.
If only mAh is available, confirm the reference voltage and the corresponding energy with the manufacturer.

Does this cover direct USB or 12V output?

This page models the AC inverter path.
Direct DC and USB use different output limits and loss paths, so do not apply the AC efficiency and output verdict to those connections.

Will all devices work if capacity is sufficient?

Energy sufficiency alone does not establish operation.
Check running and surge output, unknown items, voltage, frequency, waveform, VA and power factor, surge duration and port limits for the exact model.

Why does the table show demand after reserve is reached?

The interval table describes the energy required to perform the entire plan.
Later demand remains visible so you can see the total capacity shortfall.

Is reserve time the actual shutdown time?

It is an energy estimate using averaged duty.
Real cycling, protection circuits, temperature and output overload can change actual operation.
Do not use it to determine medical life-support or UPS suitability.

What can I save for a manufacturer check?

Download the TXT power and quote report.
It contains the appliance inputs, interval demand, both product specifications, quote and confirmation states, results and model boundaries.
Supply the manual and relevant measurements with it.

Sources, verification date and updates

Sources were checked on 2026-09-15.
EcoFlow’s guide supports separating energy, simultaneous loads and startup requirements; Jackery’s FAQ illustrates a product-specific runtime estimate that allows for losses.
The calculator’s 80%/90% efficiencies, 5W idle draw, reserve assumptions and prices are independent fictional scenarios, not shared manufacturer standards.

Review these references quarterly or when manuals change.
No statutory electricity tariff, tax, subsidy or fixed-installation design standard enters the formulas.
Recheck current model performance and quotes before purchase; fixed wiring and medical life-support power design are outside this calculator’s scope.

Enter the appliances and save a comparison

Check running and startup watts for essential devices, place their usage windows, then enter each product’s efficiency, output and quote.
If capacity or output is insufficient, adjust the schedule or product specifications and compare again.
Use the saved report to check the figures against the seller’s and manufacturer’s information.

Related calculators